Technical parameters: | BLUE 100kW280Ah-T1 | BLUE 150kW280Ah-T1 |
|
|
|
| DC | |
Battery voltage range | 500 V-850 V | |
Maximum current | 220 A | 330 A |
Photovoltaic input | ||
Maximum photovoltaic input voltage | 500 V | |
Maximum photovoltaic power | 120 kW | 180 kW |
Mppt voltage range | 200 V ~ 500 V | |
Number of MPPT | 2 | 3 |
| ||
| Energy storage battery | |
Cell type | LFP 280 Ah | |
Nominal voltage | 749 VDC | |
Nominal power | 1.12 MWh (maintenance from the interior) 1.68 MWh (maintenance from the exterior) | |
| ||
| AC (on-grid) | |
Maximum apparent power | 110 kVA | 165 kVA |
Rated output power | 100 kW | 150 kW |
Rate voltage | 400 V | |
Voltage range | 320 V-460 V | |
Maximum current | 144 A | 217 A |
Rated frequency | 50/60 Hz | |
Frequency range | 45-55/55-65 Hz | |
THDi | <3% | |
Power Factor | 1 leading ~ 1 lagging (settable) | |
AC system | 3W+N+PE | |
| ||
| AC (off-grid) | |
Rated voltage | 400 V | |
THDU | ≤ 3% linear | |
Rated frequency | 50/60 Hz | |
Overload capacity | 110% long-term | |
| ||
| General data | |
Maximum efficiency | 96.00% | |
Degrees of protection | IP55 | |
Noise | <65dB | |
Ambient temperature | -30 ℃~ +55 ℃ | |
Cooling mode | temperature controlled forced air cooling | |
Relative humidity | 0 ~ 95% non condensing | |
Altitude for product operation | 5000 m (Rating reduction occurs when the altitude for product application rises above 3000 m.) | |
Battery compartment dimension (mm) | 6058*2438*2591 | |
Isolation transformer | available | |
Self power consumption after system shut-down | <500W | |
| ||
| Display | |
Display | TP LCD | |
Bms communication interface | RS485/CAN | |
Local communication | RS485/TCP/IP | |